Connect the coil wire of the magnetic suction cup, remove the undervoltage relay housing, measure the resistance at both ends of the coil, and the needle still indicates normal, indicating that the undervoltage relay coil is not disconnected, and then check whether the relay is mechanically stuck. Then turn off the upper power switch, and use the multimeter AC gear to measure the voltage on the transformer side to be 135V. Under normal circumstances, the DC voltage output by the bridge rectifier should be 110V. At this time, there is no voltage output. Disconnect the main power switch and use the multimeter resistance to measure the four rectifier diodes separately, and find that two of them have problems. Weld the wires connecting the diodes, remove the diodes, and measure and check again, proving that the pipes are broken. Replace two new secondary tubes, connect the wires, and check whether the welding is firm.